Minnesota Power
 
Minnesota Power proudly serves 141,000 electric customers in Northeastern Minnesota and Northern Wisconsin.
 
Power of One
one home
one home

New Construction (Triple E)
 
   
   
Tier I & Tier II/ENERGY STAR® Program Standards
 
 

(Summary Table) See below for more detail

 
Tier I
Tier II and ENERGY STAR®
Minimum Insulation Requirements (Prescriptive & Performance Standards)
Attic
R-44
R-50
Cathedral Ceiling< 50% ceiling area
R-40
R-40
Cathedral Ceiling 100% of ceiling area
R-44
R-50
Exterior Walls3
R-21 cavity
R-24 cavity or R-20 continuous
Rim Joist Continuous
R-15 cavity or R-10 continuous
R-20 cavity or continuous
Foundation/Basement Wall
R-10
R-19
Slab Perimeter
R-10
R-10
Under Slab
R-10
R-10
Floor Over Exterior Space
R-24 cavity plus R-5 continuous
R-30 cavity plus R-5 continuous
Floor Over Unconditioned Space
R-24
R-30
Total Conditioned Floor Area
no limitations
1000-4000ft2
Air Tightness
< .25 cfm/ft2 @ 50 pascals
< .20 cfm/ft2 @ 50 pascals
Window Requirements
Window U-value
< .35
< .33 or <.28
Window SHGC
no requirements
> .30 or >.24
Window Distribution
no requirements
< 62.5%
Max Window Area1,2
no requirements
max 18%
Minimum Equipment Requirements (HVAC)
Gas Furnace Heating (forced air)
not allowed on tier 1 homes
> 92% AFUE with ECM motor
Gas Boiler Heating (hot water)
not allowed on tier 1 homes
> 85 % AFUE
Electric Heating
any
any
Electric Cooling (SEER)4
> 14
> 14
Air-to-Air Heat Exchanger
> 76% HRV or ERV
> 76% HRV or ERV
Thermostats for Forced Air5
ENERGY STAR Programmable
ENERGY STAR Programmable
Water Heater Requirements
Electric
Gas
40 Gallon
no requirements
0.93
0.62
50 Gallon
no requirements
0.92
0.59
60 Gallon
no requirements
0.91
0.57
80 Gallon
no requirements
0.89
0.53
Gas Instantaneous (tankless)
no requirements
n/a
any
Additional Requirements
Compliance with Thermal Bypass Checklist6
yes
yes
Duct Location
any location acceptable
conditioned space only
Duct Insulation
R-8
R-8
ENERGY STAR Lighting
5 fixtures required
5 fixtures required
ENERGY STAR Dishwasher
required
required
ENERGY STAR Clotheswasher
required
required
ENERGY STAR Refrigerator
required
required
See footnotes below
top

PRESCRIPTIVE STANDARDS
(R-values listed for insulation only)
(> means equal to or greater than. < means equal to or less than)

1. Foundation/Basement Wall and Slab on Grade Foundation Wall:
Minimum R-10 to footings. Insulation must extend to top of foundation wall and be securely attached. Required protection of exterior foam from sunlight and physical abuse and the installation of drainage materials along exterior walls to keep water away from the foundation.
Tier II/ENERGY STAR: Minimum R-19 on entire foundation wall.

2. Slab on Grade: Floating slab-R-10 under entire slab and R-10 on slab edge.

3. Basement slab or concrete floor: Minimum R-10 under entire slab. Continuous vapor barrier/retarder under entire slab for moisture and radon control.
Tier II/ENERGY STAR: same as above

4. Floors over exterior space: R-24 plus R-5 continuous (rigid foam). Continuous air barrier required.
Tier II/ENERGY STAR: R-30 plus R-5 continuous (rigid foam). Continuous
air barrier required.

Floors over unconditioned space: (i.e., crawl space and tuck under garage). R-24 and continuous air barrier required.
Tier II/ENERGY STAR: R-30 and continuous air barrier required.

5. Exterior Walls (insulation only): minimum R-21 cavity.
Tier II/ENERGY STAR: R-24 cavity or R-20 continuous.

6. Exterior wind barrier (house wrap): Continuous or sealed wrap applied on the exterior of the structure, extending from bottom of rim joist to top plate. Also, the barrier should extend to the top of the attic insulation and cover cantilevered floors and bay windows. All seams must be taped with a high quality builder tape. The house wrap shall have a perm rating of greater than 1.0.

7. Ceiling/Attic (insulation only): minimum R-44 (insulation only) – (must meet winter design performance criteria as specified by Minnesota State Energy Code) with energy truss or raised heel.
Tier II/ENERGY STAR: R-50 blown

Cathedral Ceiling < 50% ceiling area: R-40
Tier II/ENERGY STAR: same as above (R-40)
Cathedral Ceiling 100% of ceiling area: R-44
Tier II/ENERGY STAR: R-50

a. Warm air bypasses (i.e., soil stacks, electrical penetrations, chimney and vent chaseways, etc.) should be sealed to maintain the integrity of the vapor barrier/retarder and to minimize heat loss and condensation in cold attic.
b. A solid wind wash barrier shall be provided at the exterior edge of attic insulation to prevent air intrusion into the attic insulation.

8. Rim Joist: minimum R-15 cavity or R-10 continuous. Continuous interior/warm side vapor/air barrier sealed in place on all rim joist areas
Tier II/ENERGY STAR: R-20 cavity or continuous. Continuous vapor/air barrier sealed in place on all rim joist areas

9. Windows: Minimum standards < U .35 (overall unit value)
Tier II/ENERGY STAR: < U .33 (overall unit value) and Solar Heat Gain Co-efficient (SHGC) > .30 or < U .28 and SHGC > .24 Maximum allowable window area: 18% (total window area to conditioned floor area ratio)

10. Moisture Control: A continuous vapor barrier of less than 1.0 perm rating shall be installed on the winter warm side of exterior walls, ceilings and floors over unconditioned space. All bypasses caused by electrical and plumbing installations must be sealed to maintain the integrity of the vapor barrier. Also, a 6 mil polyethylene or other approved vapor barrier material must be installed under the entire surface area of the slab. Appendix 5 lists the perm rating of common building materials.

11. Air Quality Control/Ventilation: The provision of adequate ventilation in residential buildings can only be assured with a central, whole house, pressure balanced, mechanical ventilation system. There is a need to assume a minimum continuous ventilation rate to control the level of indoor air and pollutants generated by occupants or by sources with no fixed or identifiable location. This is accomplished by insuring a minimum level of makeup air. There is also a need to remove some contaminants that are generated at fixed locations, such as kitchens and bathrooms. The minimum rate for whole house ventilation, considering mechanical ventilation capacity and natural air leakage, is .35 ACH. Spot ventilation (kitchen and bathrooms) provided on an intermittent basis must be capable of 100 cfm in the kitchen and 50 cfm in the bathrooms.

11.1 Required Ventilation Options:
Heat Recovery Ventilator (HRV) or Energy Recovery Ventilator (ERV), also known as air-to-air heat exchangers or whole house mechanical ventilation systems. System balancing is required and an optional incentive is available for the presence of a balancing verification label on the unit.
Tier II/ENERGY STAR: Minimum active recovery efficiency > 76%. (see Appendix 4 listing minimum requirements for ventilation systems.)

12. Space Heating and Domestic Hot Water

12.1 Space Heating
Electric space heating on the firm, dual fuel or storage/off peak rate (i.e., baseboard, slab heat, boiler, furnace, storage units, ground source heat pump, etc.). Ground source heat pumps must have a minimum 3.3 COP on closed loop systems and 3.6 COP on open loop systems.

Gas space heating: minimum 92% AFUE for furnaces and 85% AFUE for hot water boilers. ENERGY STAR programmable thermostat required on all gas forced air furnaces.

Ductwork located in unconditioned spaces require thorough sealing of all seams and joints and insulated to a minimum of R-8.

12.2 Fossil Fuel Appliances
Combustion appliances (i.e., fireplaces, stoves, water heaters) must have an independent source of makeup air directly connected to the combustion chamber (sealed combustion).

12.3 Domestic Hot Water
The builder/owner is required to install a high efficiency hot water heater and meet all state requirements for water conservation related to toilets, showerheads and faucet aerators. Also recommended to install pipe wrap insulation on the hot and cold pipes leading to and from the water heater.
Tier II/ENERGY STAR: (see Appendix 1 for water heater efficiency requirements)

13. ENERGY STAR® Lighting and Appliances

The home must have a minimum of five (5) ENERGY STAR® light fixtures and the refrigerator, dishwasher and clothes washer must be ENERGY STAR® rated.

14. Building Orientation (optional)

Forty percent of glass area must be within 30 degrees south facing for optimum solar gain. This is an optional standard that qualifies for an additional $200 rebate. (Patio and slider doors are considered as window area)

15. Drain Water Heat Recovery Device (optional)

A drain water heat recovery device captures heat from the drain water and uses it to preheat incoming cold water. GFX unit or equivalent qualifies for an additional $100 rebate. This is an optional standard.

TRIPLE E PERFORMANCE STANDARDS

1. Air Tightness Performance Standard

Minimum air leakage not to exceed .25 cfm/ft2 at 50 pascals. Tier II/ENERGY STAR: not to exceed .20 cfm/ft2 at 50 pascals. Tier III: not to exceed .15 cfm/ft2 at 50 pascals (eligible for additional rebate incentive)

Blower door analysis (depressurization technique) is completed during the final inspection. Ductwork leakage in unconditioned space cannot exceed 12% leakage at 25 pascals

ENERGY STAR Qualified Homes Equivalent Program Footnotes
For Use in the State of Minnesota

1. All decorative glass and skylight window area counts toward the total window area to abovegrade conditioned floor area (WFA) ratio. For homes with conditioned basements, the following equation must be used to determine the allowable window area: Allowable Window Area = 18% x Total Conditioned Floor Area x FA, where FA = (Above-grade thermal boundary gross wall area) / (Above-grade thermal boundary gross wall area + 0.5 x belowgrade thermal boundary gross wall area). For example, for a one-story home with a conditioned basement, 1000 sq. ft. of conditioned space per floor, 8' floor to ceiling height, and 6' below grade basement depth, the following window area would be allowed: 18% * 2000 sq. ft. * [(8 ft. + 2 ft.) * house perimeter] / [(8 ft. + 2 ft. + 0.5 * 6 ft) * house perimeter] = 277 sq. ft.

2. Up to 0.75% WFA may be used for decorative glass that does not meet ENERGY STAR requirements. For example, a home with total above-grade conditioned floor area of 2,000 sq. ft. may have up to 15 sq. ft. (0.75% of 2,000) of decorative glass.

3. Walls constructed of Insulated Concrete Forms (ICF) or Structurally Insulated Panels (SIP) with a nominal insulation level of at least R-20 may be used in place of the required R-24 wood-frame walls.

4. Central cooling equipment should have a SEER rating of 14 or greater and must be properly installed by a contractor who has been trained through the Minnesota Power HVAC rebate program. Visit www.mnpower.com for more information, or contractors can call 1-800-969-9322, ext. 167 to participate.

5. In homes with heat pumps that have programmable thermostats, the thermostat must have “Adaptive Recovery” technology to prevent the excessive use of electric back-up heating.

6. The Thermal Bypass Inspection Checklist must be completed for homes to earn the ENERGY STAR label. The Checklist requires visual inspection of framing areas where air barriers are commonly missed and inspection of insulation to ensure proper alignment with air barriers, thus serving as an extra check that the air and thermal barriers are continuous and complete.

7. Envelope leakage must be determined by a RESNET-certified rater using a RESNETapproved testing protocol.

8. To determine domestic hot water (DHW) EF requirements for additional tank sizes, use the following equations: Gas DHW EF ≥ 0.69 – (0.002 x Tank Gallon Capacity): Electric DHW EF ≥ 0.97 – (0.001 x Tank Gallon Capacity). In addition, any gas or electric instantaneous water heater may be used in place of a strong water heater.

 
© Copyright 2008    ALLETE, Inc.     Privacy     Site Map     Contact Us