PRESCRIPTIVE STANDARDS
(R-values listed for insulation only)
(> means equal to or greater than. < means equal to or less than)
1. Foundation/Basement Wall and Slab on Grade Foundation Wall:
Minimum R-15 to footings. Insulation must extend to top of foundation wall
and be securely attached. Required protection of exterior foam from sunlight
and physical abuse and the installation of drainage materials along exterior
walls to keep water away from the foundation.
Tier II: Minimum R-20 on entire foundation wall.
2. Slab on Grade: Floating slab R-15 under entire slab and R-15 on slab edge. Note: all designs need to be engineered to be frost protected.
Tier II: Floating slab R-20 under entire slab and R-20 on slab edge..
3. Basement slab or concrete floor: Minimum R-15 under entire slab.
Continuous vapor barrier/retarder under entire slab for moisture and radon
control.
Tier II: Minimum R-20 under entire slab.
4. Floors over exterior/unheated space: R-24 plus R-5 continuous (rigid foam).
Continuous air barrier required.
Tier II: R-30 plus R-5 continuous (rigid foam). Continuous air barrier required.
Floors over heated space (i.e., heated crawl space and heated
garage): R-24 cavity and continuous air barrier required.
Tier II: R-30 cavity and continuous air barrier required.
5. Exterior Walls (insulation only): minimum R-21 cavity.
Tier II: R-21 cavity plus R-5 or R-20 continuous.
6. Exterior wind barrier (house wrap): Continuous or sealed wrap applied
on the exterior of the structure, extending from bottom of rim joist to the bottom of the exterior soffit. Also, the house wrap should cover all exterior sheathing material and
cover cantilevered floors and bay windows. All seams must be taped with a
high quality builder tape. The house wrap shall have a perm rating of greater
than 1.0.
7. Ceiling/Attic (insulation only): minimum R-50 blown (insulation only) – (must
meet winter design performance criteria as specified by Minnesota State
Energy Code) with energy truss or raised heel.
Tier II: R-60 blown
a. Warm air bypasses (i.e., soil stacks, electrical penetrations, chimney and
vent chaseways, etc.) should be sealed to maintain the integrity of the
vapor barrier/retarder and to minimize heat loss and condensation in
cold attic.
b. A solid wind wash barrier shall be provided at the exterior edge of attic
insulation to prevent air intrusion into the attic insulation.
8. Rim Joist: minimum R-20 cavity or R-15 continuous. Continuous
interior/warm side vapor/air barrier sealed in place on all rim joist areas
Tier II: R-20 cavity plus R-5 continuous or R-20 continuous. Continuous vapor/air
barrier sealed in place on all rim joist areas.
9. Windows: Minimum standards < U .33 (overall unit value)
Tier II: < U .30 (overall unit value)
Maximum allowable window area: 18% (total window area to conditioned
floor area ratio)
10. Moisture Control: A continuous vapor barrier of less than 1.0 perm rating shall be installed on
the winter warm side of exterior walls, ceilings and floors over unconditioned
space. All bypasses caused by electrical and plumbing installations must be
sealed to maintain the integrity of the vapor barrier. Also, a 6 mil
polyethylene or other approved vapor barrier material must be installed
under the entire surface area of the slab. Appendix 5 lists the perm rating of
common building materials.
11. Air Quality Control/Ventilation: The provision of adequate ventilation in residential buildings can only be
assured with a central, whole house, pressure balanced, mechanical
ventilation system. There is a need to assume a minimum continuous
ventilation rate to control the level of indoor air and pollutants generated by
occupants or by sources with no fixed or identifiable location. This is
accomplished by insuring a minimum level of makeup air. There is also a
need to remove some contaminants that are generated at fixed locations, such
as kitchens and bathrooms.
The minimum rate for whole house ventilation, considering mechanical
ventilation capacity and natural air leakage, is .35 ACH. Spot ventilation
(kitchen and bathrooms) provided on an intermittent basis must be capable
of 100 cfm in the kitchen and 50 cfm in the bathrooms.
11.1 Required Ventilation Options:
Heat Recovery Ventilator (HRV) or Energy Recovery Ventilator (ERV),
also known as air-to-air heat exchangers or whole house mechanical
ventilation systems. System balancing is required and an optional
incentive is available for the presence of a balancing verification label
on the unit.
Tier I: Minimum apparent sensible effectiveness ≥ 76% at -13°F
(see Appendix 4 listing minimum requirements for ventilation systems.)
Tier II: Minimum apparent sensible effectiveness ≥ 80% at -13°F.
(see Appendix 4 listing minimum requirements for ventilation systems.)
12. Space Heating and Domestic Hot Water
12.1 Space Heating
Electric space heating on the firm, dual fuel or storage/off peak rate
(i.e., baseboard, slab heat, boiler, furnace, storage units, ground source
heat pump, etc.). Ground source heat pumps must be ENERGY STAR® rated as listed at www.energystar.gov.
Backup Gas space heating: minimum 90% AFUE for furnaces with ECM motors and 90% AFUE
for hot water boilers. ENERGY STAR programmable thermostat
required on all gas forced air furnaces.
Tier I: Ductwork located in unconditioned spaces require thorough sealing of
all seams and joints with jacketed insulation to a minimum of R-8.
Tier II: All ductwork must be in conditioned living space.
12.2 Fossil Fuel Appliances
Combustion appliances (i.e., wood, stoves, water heaters) must
have an independent source of makeup air directly connected to the
combustion chamber (sealed combustion). Houses with wood stover or corn pellet stoves must meet code requirements.
12.3 Domestic Hot Water
The builder/owner is required to install a high efficiency hot water
heater and meet all state requirements for water conservation related
to toilets, showerheads and faucet aerators. Also recommended to
install pipe wrap insulation on the hot and cold pipes leading to and
from the water heater.
Tier II: (see Appendix 1 for water heater efficiency
requirements)
13. ENERGY STAR® Lighting and Appliances
The home must have a minimum of five (5) ENERGY STAR® light fixtures and the refrigerator, dishwasher and clothes washer must be ENERGY STAR® rated.
14. Building Orientation (optional)
Forty percent of glass area must be within 30 degrees south facing for
optimum solar gain. This is an optional standard that qualifies for an
additional $200 rebate. (Patio and slider doors are considered as window
area)
15. Drain Water Heat Recovery Device (optional)
A drain water heat recovery device captures heat from the drain water and
uses it to preheat incoming cold water. PowerPipe, GFX unit or equivalent qualifies for
an additional $400 rebate. This is an optional standard.
TRIPLE E PERFORMANCE STANDARDS
1. Air Tightness Performance Standard
Minimum air leakage not to exceed .25 cfm/ft2 at 50 pascals.
Tier II: not to exceed .20 cfm/ft2 at 50 pascals. Note: Achieving air tightness levels of .10 cfm/ft2 at 50 pascals (eligible for additional rebate
incentive)
Blower door analysis (depressurization technique) is completed during the
final inspection. |